SF6 Gas Insulated Ring Main Unit
SF6 Gas Insulated Switch Gear
Compact design, customizable installation interface to user'sneed, convenient and reliable.
Suited for different indoor and outdoor installation requirements
Up to three sets of contact switches.
RS485 remote transmission function, convenient remote monitoring
Temperature compensated
Case diameter: | 64mm |
Scale range: | 0 ~ 2bar abs.(customizable) |
Accuracy of indication : | ±1.5%FS(+20±1℃)±2.5%FS(-20℃~+60℃)(gas) |
Ambient conditions: | -20℃~ +60℃ realative humidity ≤95% |
Degree of protection: | IP65 |
Leakage rate: | ≤1 x 10-9Pa·m3/s (Helium leakage inspection) |
Process connection: | M20 x 1.5 (customizable) |
Installation mode: | radial or axial |
Insulation resistance: | >100MΩ (DC500V) |
withstand voltage: | 2kV, 50/60Hz, 1min |
Contact type: | Magnetic snap-action contact (Up to 3 set of contacts.s ,NO & NC) |
Impact rating: | 30 g |
Rated Power: | 30VA |
Max switching voltage: | 380V |
Max switching current: | 1A |
Weight: | ≈0.9kg |
Pressure element: | Bourdon tube |
Technical Parameters for Remote Module
Operating voltage: 10~30VDC
Power consumption :<0.5W
Communication mode: RS485
Communication protocol: Modbus RTU
Baud rate: 9600bps
EMC Class:
IEC61000-4-2:Level 4
IEC61000-4-3:Level 3
IEC61000-4-4:Level 4
IEC61000-4-5:Level 3
IEC61000-4-6:Level 3
IEC61000-4-8:Level 5
Measuring range
Wider temperature range: -40℃ ~ +60℃
Outlet mode and cable length
Installation method
High altitude environment application
Measuring Medium:SF6, Air, N2, SF6+N2 and other gases
Optional measurement accuracy:±1.0%FS(+20±1℃),±2.5%FS(-20℃~+60℃)(gas phase)