How to Select the Calibrator of SF6 Gas Density Relay?

Table of Content [Hide]

    First of all, let's understand the basic principle of calibrator of SF6 gas density relay. SF6 gas in SF6 high voltage circuit breaker is sealed in a fixed container. Under the rated pressure of 20℃, it has a certain density value, which is within the range of various allowable conditions for circuit breaker operation. Although the pressure of SF6 gas varies with temperature, the density value of SF6 gas remains constant. Because the insulation characteristics and arc extinguishing performance of SF6 circuit breaker largely depend on the density of SF6 gas, the monitoring of SF6 density is particularly important. In order to achieve the purpose of frequent density monitoring, the national standard stipulates that SF6 circuit breaker should be equipped with SF6 relay. Density relay plays a role of control and protection, so it is particularly important to use the calibrator of SF6 gas density relay to calibrate the density relay regularly.


    SF6 relay calibrator mainly measures four parameters for density relay calibration. The testing process of these four parameters is as follows.


    1. Calibrate the locking recovery value of SF6 relay


    Under the ambient temperature, when SF6 relay is at zero pressure, the SF6 relay is charged slowly at a certain speed. When the latching relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃, which is the latching recovery value of SF6 relay.


    2. The alarm recovery value of SF6 relay


    Continue to charge SF6 relay slowly at a certain speed. When the alarm relay of density relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the alarm recovery value of SF6 relay.


    3. Calibrate the alarm value of SF6 relay

    Under the ambient temperature, when the pressure in SF6 relay is greater than the alarm recovery value, the gas is slowly deflated at a certain speed. When the alarm relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃. The equivalent pressure value at 20℃ is the alarm value of SF6 relay.


    4. Calibrate the locking value of SF6 relay


    Continue to slowly deflate the SF6 relay at a certain speed. When the latching relay of SF6 relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the latching value of SF6 relay.

    A high-quality calibrator of SF6 gas density relay should have the above four technical indicators featuring efficient and stable testing, good repeatability, cheap and fine.

    References

    Related Article for Reference

    What Is the Important Role of SF6 Laser Moisture Meter?
    To understand the important role of SF6laser moisture meter, it is necessary to first understand what SF6 is. SF6 is an insulating gas widely used in the field of high voltage and ultra high voltage, ...
    Tue 12 2023
    SF6 Density Relay Signal Detection Interface Application
    Ⅰ. Requirements for the development of SF6 density relayThe research focuses on the development of the signal detection interface device for SF6 density relays. The following technical indicators nee...
    Tue 02 2023
    SF6 Gas Density Online Monitoring and Alarm System
    Most devices containing SF6 gas are installed in rooms, where the indoor ventilation rate is relatively slow. Once SF6 gas leaks, it will accumulate in the room and is not easily released. SF6 gas its...
    Sat 08 2023
    Lanso Instruments INC.
    233 W 1st St #210, North Vancouver, Canada
    info@lansoinstruments.com
    233 W 1st St #210, North Vancouver, Canada
    info@lansoinstruments.com