How to Select the Calibrator of SF6 Gas Density Relay?

First of all, let's understand the basic principle of calibrator of SF6 gas density relay. SF6 gas in SF6 high voltage circuit breaker is sealed in a fixed container. Under the rated pressure of 20℃, it has a certain density value, which is within the range of various allowable conditions for circuit breaker operation. Although the pressure of SF6 gas varies with temperature, the density value of SF6 gas remains constant. Because the insulation characteristics and arc extinguishing performance of SF6 circuit breaker largely depend on the density of SF6 gas, the monitoring of SF6 density is particularly important. In order to achieve the purpose of frequent density monitoring, the national standard stipulates that SF6 circuit breaker should be equipped with SF6 relay. Density relay plays a role of control and protection, so it is particularly important to use the calibrator of SF6 gas density relay to calibrate the density relay regularly.


SF6 relay calibrator mainly measures four parameters for density relay calibration. The testing process of these four parameters is as follows.


1. Calibrate the locking recovery value of SF6 relay


Under the ambient temperature, when SF6 relay is at zero pressure, the SF6 relay is charged slowly at a certain speed. When the latching relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃, which is the latching recovery value of SF6 relay.


2. The alarm recovery value of SF6 relay


Continue to charge SF6 relay slowly at a certain speed. When the alarm relay of density relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the alarm recovery value of SF6 relay.


3. Calibrate the alarm value of SF6 relay

Under the ambient temperature, when the pressure in SF6 relay is greater than the alarm recovery value, the gas is slowly deflated at a certain speed. When the alarm relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃. The equivalent pressure value at 20℃ is the alarm value of SF6 relay.


4. Calibrate the locking value of SF6 relay


Continue to slowly deflate the SF6 relay at a certain speed. When the latching relay of SF6 relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the latching value of SF6 relay.

A high-quality calibrator of SF6 gas density relay should have the above four technical indicators featuring efficient and stable testing, good repeatability, cheap and fine.

Related Article for Reference

Why is the Diaphragm Pressure Gauge So Popular in the Market?
Ⅰ. Why are diaphragm pressure gauges so popular?Diaphragm pressure gauge-an instrument familiar to many industrial employees, and the sales of hygienic diaphragm pressure gauges in the market have al...
Thu 04 2021
Application of Online Monitoring System for SF6 Gas Density in GIS Equipment
GIS (Gas Insulated Switchgear) equipment plays a vital role in the power industry, ensuring efficient transmission and distribution of electricity. To maintain the safety and reliable operation of the...
Sat 07 2023
What is SF6 Gas Density Monitoring and How to Eliminate Sparks on SF6 Gas Density Relay Contacts?
Density of gas is an important working structure of high-pressure equipment. If the required density of gas does not exist, the safe operation of the current working environment cannot be guaranteed. ...