How to Select the Calibrator of SF6 Gas Density Relay?

First of all, let's understand the basic principle of calibrator of SF6 gas density relay. SF6 gas in SF6 high voltage circuit breaker is sealed in a fixed container. Under the rated pressure of 20℃, it has a certain density value, which is within the range of various allowable conditions for circuit breaker operation. Although the pressure of SF6 gas varies with temperature, the density value of SF6 gas remains constant. Because the insulation characteristics and arc extinguishing performance of SF6 circuit breaker largely depend on the density of SF6 gas, the monitoring of SF6 density is particularly important. In order to achieve the purpose of frequent density monitoring, the national standard stipulates that SF6 circuit breaker should be equipped with SF6 relay. Density relay plays a role of control and protection, so it is particularly important to use the calibrator of SF6 gas density relay to calibrate the density relay regularly.


SF6 relay calibrator mainly measures four parameters for density relay calibration. The testing process of these four parameters is as follows.


1. Calibrate the locking recovery value of SF6 relay


Under the ambient temperature, when SF6 relay is at zero pressure, the SF6 relay is charged slowly at a certain speed. When the latching relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃, which is the latching recovery value of SF6 relay.


2. The alarm recovery value of SF6 relay


Continue to charge SF6 relay slowly at a certain speed. When the alarm relay of density relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the alarm recovery value of SF6 relay.


3. Calibrate the alarm value of SF6 relay

Under the ambient temperature, when the pressure in SF6 relay is greater than the alarm recovery value, the gas is slowly deflated at a certain speed. When the alarm relay of SF6 relay operates, the pressure value under the current ambient temperature is recorded and converted into the equivalent pressure value at 20℃. The equivalent pressure value at 20℃ is the alarm value of SF6 relay.


4. Calibrate the locking value of SF6 relay


Continue to slowly deflate the SF6 relay at a certain speed. When the latching relay of SF6 relay operates, record the pressure value under the current ambient temperature and convert it into the equivalent pressure value at 20℃, which is the latching value of SF6 relay.

A high-quality calibrator of SF6 gas density relay should have the above four technical indicators featuring efficient and stable testing, good repeatability, cheap and fine.

Related Article for Reference

Inspection of SF6 Gas Density Relay
SF6 gases are increasingly used in a variety of high-voltage electrical equipment due to their excellent insulation and arcing properties. Become the preferred insulation and arcing medium for today&#...
Thu 09 2021
Problems Related to the Field Test of SF6 Gas Density Monitor
In the SF6 gas density monitor circuit breaker, the decisive factor for its electrical strength and arc extinguishing performance is the gas density, and the main component reflecting the change of th...
Tue 05 2021
Notes on Instructions for SF6 Relay and Gas Density Meter Operation
1. Sf6 relay and gas density meter can accurately measure the sf6 gas density (or pressure) value only after the sf6 equipment is out of operation and the internal and external temperatures of the equ...
Tue 11 2021
Lanso Instruments INC.
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com