language
Contact Us

Principles and Techniques for Calibration of SF6 Gas Density Relays

Table of Content [Hide]

    Calibration principle of SF6 gas density relay


    Temperature compensation principle of density relay


    SF6 gas has excellent insulation and arc extinguishing properties, making it a natural "cold field champion." The insulation and arc extinguishing properties of SF6 gas depend on its density, according to the ideal gas equation PV=nRT.


    The density relay of SF6 gas compensates for the influence of temperature changes. In other words, even with the same amount of SF6, the displayed pressure remains constant despite temperature variations. How is the compensation for temperature changes achieved?


    Simply put, temperature changes cause changes in the Bourdon tube and bimetallic strip, which cancel out each other's effects, keeping the pointer of the gauge unchanged.


    In a closed container, the pressure of SF6 gas at a certain temperature can represent the density of SF6 gas. For the sake of standardization, it is customary to use the pressure of SF6 gas at 20°C as the reference value. During on-site calibration, the measured pressure values at different ambient temperatures need to be converted into their corresponding values at 20°C in order to assess the performance of the SF6 gas density relay. Calibration is achieved by inflating and deflating the relay to achieve overpressure value, alarm value, and locking value.


    When the pointer of the SF6 density relay is at zero, slowly and uniformly inflate the relay. When the SF6 density relay triggers a locking (alarm) action, record the pressure value at the current ambient temperature and convert it to the equivalent pressure value at 20°C. This equivalent pressure value represents the locking (alarm) response value of the SF6 density relay.


    Under ambient temperature, when the internal pressure value of the SF6 density relay is higher than the alarm (locking) response value, start slowly and uniformly deflating. When the SF6 density relay sends an alarm (locking) signal, record the pressure value at the current ambient temperature and convert it to the equivalent pressure value at 20°C. This equivalent pressure value represents the alarm (locking) value of the SF6 density relay.


    Testing technique of SF6 gas density relay


    Open the instrument box cover and take out the test tubing and wiring from the accessory package. Connect the instrument's grounding wire, temperature sensor connection wire, signal acquisition wire, and test tubing in order.


    Connect the SF6 gas density relay to be calibrated, the pressure gauge or density gauge to be tested, and the instrument's test interface. Check and confirm that all connections are correct, then turn on the instrument's power to enter the measurement interface.


    Enter the density relay calibration function, set the test parameters according to the rated parameters of the SF6 density relay to be calibrated, check the test parameters for accuracy, and click "Test." The instrument will automatically complete the test.


    Table comparing the indication accuracy level and allowable error of the density relay

    level of accuracy

    Allowable error (calculated as a percentage of the range)

    20℃±1℃

    -25℃~+60℃


    1.0

    ±1.0%

    ±2.5%


    1.6

    ±1.6%

    ±2.5%



    References

    Related Article for Reference

    The Custody, Transportation, and Frequently Asked Questions on SF6 Relay Calibrator
    SF6 Relay Verifier is an important equipment in the electric power industry, used to ensure the accuracy and reliability ofSF6 Relay. When using and maintaining this critical equipment, attention shou...
    Fri 12 2023
    On What Occasions and Locations Is It Necessary to Install SF6 Density Monitor?
    SF6 Density Monitor is a critical safety device widely used in SF6 switchgear rooms, SF6 circuit breaker chambers, combined apparatus rooms (GIS rooms), SF6 main transformer rooms, and SF6 gas laborat...
    Thu 04 2024
    How to Calibrate the SF6 Gas Density Relay? Why Is Regular Calibration Necessary?
    How to Verify SF6 Gas Density Relays?Since SF6 gas density relays are typically installed alongside switches in the field and are not easy to disassemble, as frequent disassembly can lead to interface...
    Thu 09 2023
    Lanso Instruments INC.
    233 W 1st St #210, North Vancouver, Canada
    info@lansoinstruments.com
    233 W 1st St #210, North Vancouver, Canada
    info@lansoinstruments.com