language
Contact Us

DT26 Density Transmitter

DT26 Density Transmitters are used to monitor SF6 gas density in sealed tanks. It can provide multiple solutions to support new substations and the renovation and upgrading of existing substations.
DT26 Density Transmitter
  • DT26 Density Transmitter
  • DT26 Density Transmitter
Share It :

Drawing of DT26 Density Transmitter


DT26 Density Transmitter



Application of DT26 Density Transmitter


  • SF6Gas Insulated Switchgear (GIS)

  • SF6 Insulated Circuit Breakers

  • SF6 Insulated Pole-Mounted Switch

  • SF6 Insulated Transformer

  • SF6 Insulated Current Transformer or Voltage Transformer

  • SF6 Gas Insulated Busbar Systems

  • SF6 Insulated Inflatable Cabinet

  • SF6 Insulated RMU


Features of DT26 Density Transmitter


  • SF6 gas remote density transmitter suitable for medium and high pressure system monitoring

  • All welded sensor structure, long - term stable sealing performance

  • RS485 bus communication(MODBUS RTU)

  • The EMC characteristics of the transmitter meet the requirements of IEC 61000-4-2 to IEC 61000-4-6 standards

  • Compact design


Technical Data of DT26 Density Transmitter


1. Measuring range: 0 to 1.0MPa abs.or 0 to 0.2MPa abs.(customized)

2. Temperature measurement range:-40℃~+80℃

3. Pressure measurement accuracy:±0.5% FS

4. Temperature measurement accuracy:±1℃

5. Density (P20) measurement accuracy:±1.0%FS

6. Degree of protection: IP65

7. Ambient conditions: -40°C to 70°C, relative humidity ≤95%RH

8. Leakage rate:≤1×10-9 Pa·m3/s (Helium leakage inspection)

9. Electrical connection: Hirschmann Connector

10. Weight: 0.2kg



Technical Parameters for Remote Module

  • Power supply: 24V DC

  • Power consumption: < 0.5W

  • Communication mode: RS485  

  • Protocol: ModBus RTU

  • Baud rate: 9600bps

 

IEC61000-4-2: level 4
IEC61000-4-3:  level 3
IEC61000-4-4: level 4
IEC61000-4-5:  level 4
IEC61000-4-6:  level 3



Options of DT26 Density Transmitter


  • Pressure connection: M20 × 1.5(customizable)

  • Measuring Medium:SF6, Air, N2, SF6 + N2 and other gases


Brands We Cooperate
abb
siemens
schneider
toshiba
hyosung
Pressure Instruments Inquiry
Pictures or documents for technical requirements (optional)
Related Density Transmitter for Reference
Related News
SF6 Gas Density Monitor Helps You Quickly Detect Potential Leakage Risks
SF6 gas density monitor is a device used to detect and locate SF6 gas leaks. SF6 is a potent greenhouse gas with high thermal stability and electrical insulating properties, widely used in power equip...
Sun 06 2025
Understanding the Sulfur Hexafluoride Gas Density Monitor
Working Principle of Sulfur Hexafluoride Gas Density MonitorThe working principle of the sulfur hexafluoride gas density monitor is mainly based on the detection of the degree of gas ionization under ...
Wed 06 2025
Principle and Overview of the SF6 Relay
The Working Principle of the SF6 RelayThe working principle of the sulfur hexafluoride (SF6) gas density relay is primarily based on the relationship between the pressure and density of SF6 gas, along...
Sat 06 2025
Lanso Instruments INC.
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com