ZMJ60XDR Density Monitor

ZMJ60XDR Density Monitors are used to monitor SF6 gas density in sealed tanks. They are applied to indicate the gas density and to provide signal outputs when the den- sity reaches the set values. Furthermore, it can transmit the real-time SF6 gas density data remotely, to achieve online remote monitoring function. They are designed to monitor High Voltage systems. They can provide mul- tiple solutions to support new substations and the reno- vation and upgrading of existing substations.

    shop_iconsAdd ShopCart
    Contact us Download

    1

    SF6 Gas Insulated Swithchgear (GIS)
    SF6 Insulated Circuit Breaker
    SF6 Insulated Pole-Mounted Switch
    SF6 Insulated Transformer
    SF6 Insulation Current Transformers or Voltage Transformers
    SF6 Insulated Bus System

    Higher accuracy from reference chamber tempera- ture compensation technology.
    Suitable for indoor or outdoor installation.
    Micro-switch that can switch freely between nor- mally open and normally closed points.
    Up to 4 pairs of switches, multiple options such as double alarms and double locks can be realized, making monitoring more secure and reliable.
    High shock resistance, reducing need for oil and the potential hazard of oil leakage.
    Normally closed contact will not false alarm due to vibration.
    RS485 bus interface, easy to expand current system for telemetry and remote control functions.
    Strong EMC capability.

    Technical Parameters for Remote Module

    Operating voltage

    10~30VDC

     

     

    EMC tests

    IEC61000-4-2: Level 4

    IEC61000-4-3: Level 3

    IEC61000-4-4: Level 4

    IEC61000-4-5: Level 4

    IEC61000-4-6: Level 3

    IEC61000-4-8: Level 5

    IEC61000-4-9: Level 5

    IEC61000-4-10: Level 5

    Power consumption

    <0.5W

    Communication mode

    RS485

    Communication protocol

    Modbus RTU

    Baud rate

    9600bps

    Technical parameters

    Technical parameters

    Scale range

    -0.1 ~ 0.9MPa

    Accuracy of set pressure point

    ±10 kPa @ –30 ~ +60 ° C(gas)

    Accuracy of indication

    ±10 kPa @ –30 ~ +60 ° C(gas)

    Accuracy of transmitter

    Pressure:±0.5%FS

    Temperature:±1℃

    Pressure at 20℃: ±1.0%FS

    Degree of protection

    IP65

    Ambient condition

    -30℃ ~ +60℃ , relative humidity:≤ 95%RH

    Leakage rate

    ≤ 1×10-9 Pa-m3/s (Helium leak inspection)

    Process connection

    M20 x 1.5 (customizable)

    Installation method

    Radial or Axial

    Electrical connection

    Pluggable connector, wire diameter 0.2~2.5 mm2

    Insulation property(contact part)

    Insulation resistance: >100MΩ (DC500V)

    Withstand voltage: 2kV, 50/60Hz, 1min

    Contact type

    Microswitch

    Impact rating

    50g

    Contact electrical parameters

    10(1.5)A, 250V AC

    0.1(0.05)A, 250V DC

    Watch glass

    Laminated safety glass

    Weight

    ≈ 1.2kg

    Pressure element

    Bellow

    Pressure connections: customizable
    Nominal diameter: customizable

    Application of SF6 Gas Density Monitors in the Power Industry

    Industry Background
    Sulfur hexafluoride (SF6) gas is widely used as an insulating gas in the power industry due to its excellent properties such as high insulation performance, high electrical strength, and chemical stability. It is commonly used in high-voltage switches, isolators, circuit breakers, and other power equipment to ensure these devices can operate safely and reliably under normal and abnormal conditions.
    However, with the widespread use of SF6 gas, leakage issues have become increasingly prominent, emerging as a latent killer in the power industry. SF6 gas leakage can not only lead to power equipment failures but also pose threats to the environment and personnel safety. Consequently, the power industry has imposed higher demands on equipment maintenance and fault prevention. The installation and use of SF6 gas density monitors have become particularly important. SF6 gas density monitors can monitor the density of SF6 gas in real-time, helping operators timely detect potential safety hazards.

    The Role of SF6 Gas Density Relays
    ·Equipment Maintenance
    Traditional equipment maintenance methods often rely on manual inspections and experiential judgments, making it difficult to accurately determine the operating status of equipment. Remote SF6 gas density monitors can monitor the equipment's operating status in real-time, promptly detect abnormal SF6 gas pressures, upload the data to an online monitoring platform, and issue warnings. This provides robust data support for equipment maintenance, thereby improving the efficiency and accuracy of maintenance.
    ·Fault Prevention
    The stable operation of the power system is crucial to the normal development of the socio-economy. By installing SF6 gas density monitors, the power industry can timely discover precursors of equipment failures, such as abnormal increases or decreases in SF6 gas pressure, thereby taking preventive measures to avoid equipment damage from affecting the power system, ensuring the safe and reliable supply of electricity.
    ·Personnel Safety Protection
    Toxic and harmful gases produced from the decomposition of SF6 gas can pose threats to the health of operational personnel. By installing SF6 gas density monitors, the power industry can timely detect and manage SF6 gas leaks, ensuring the safety of staff members.
    In conclusion, SF6 gas density monitors adopt sensitive actuation methods, such as micro-switches, characterized by fast response speeds, good repeatability, and resistance to environmental interference. Additionally, SF6 gas density monitors offer high precision, ease of operation, and long service life, meeting the power industry's demands for real-time monitoring and long-term stable operation.