+86-400-820-1296
ZMJ60V Density Monitor

SF6 Gas Insulated RMU
SF6 Gas Insulated Switchgear
Compact design, customized installation interface, convenient and reliable.
Process connection customizable in accordance with customer’s demands.
Up to three sets of switching contacts can be pro- vided according to user’s needs.
Without disassembling SF6 density monitor, SF6 gas density monitor can be calibrated or replaced.
Without disassembling the screws, a person can operate independently, which is convenient
Temperature compensation for higher accuracy.
It can facilitate on-site personnel to measure mi- cro-water and supplement air for switch.
Avoid the sealing surface and sealing joint damage caused by the disassembling.
|
Technical Parameters |
|
|
Case diameter |
Φ64mm |
|
Case material |
Stainless steel |
|
Scale range |
0 to 2bar abs.(customizable) |
|
Accuracy |
±1.5%FS(+20℃ ±1℃) ±2.5%FS(-20℃~ +60℃) (gas phase) |
|
Ambient conditions |
-20° C to 60° C, relative humidity ≤ 95%RH |
|
Degree of protection |
IP65 |
|
Leakage rate |
≤ 1 × 10-9 Pa·m3/s (Helium leakage inspection) |
|
Contact type |
Magnetic snap-action contacts (up to 3 sets, NO or NC) |
|
Process connection |
M20×1.5 (customizable) |
|
Maintenance connection |
M16×1.5 (customized and additional adapter needed to the calibrator or gas tank) |
|
Installation method |
Radial or Axial |
|
Insulation properties |
Insulation resistance: >100 MΩ (500 V DC) Withstand voltage: 2kV, 50/60 Hz 1 min |
|
Contact electrical parameters |
Rated Power: 30VA |
|
Max. operating voltage |
380V |
|
Max. current |
1A |
|
Weight |
≈ 0.6kg |
|
Pressure element |
Bourdon tubes |
Different measuring ranges
Wide temperature range:-40° C to +60° C
Measuring Medium:SF6 , Air, N2, SF6+N2 and other gases
Remote transmission function
Optional measurement accuracy:±1.0%FS(+20± 1℃) , ±2.5%FS(-20℃~ +60℃)(gas phase)

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series