ZMJ60V Density Monitor

ZMJ60V Density Monitors are used to monitor the den- sity of SF6 gas in sealed tanks, and can be widely used in medium voltage switchgear, RMU. It’s suitable for out- door harsh conditions.
It can provide multiple solutions to support new sub- stations and the renovation and upgrading of existing substations.
The electrical maintenance personnel can make SF6 gas density monitor calibration or gas filling without disas- sembling SF6 density monitor.

    shop_iconsAdd ShopCart
    Contact us

    1

    SF6 Gas Insulated RMU
    SF6 Gas Insulated Switchgear

    Compact design, customized installation interface, convenient and reliable.
    Process connection customizable in accordance with customer’s demands.
    Up to three sets of switching contacts can be pro- vided according to user’s needs.
    Without disassembling SF6 density monitor, SF6 gas density monitor can be calibrated or replaced.
    Without disassembling the screws, a person can operate independently, which is convenient
    Temperature compensation for higher accuracy.
    It can facilitate on-site personnel to measure mi- cro-water and supplement air for switch.
    Avoid the sealing surface and sealing joint damage caused by the disassembling.

    Technical Parameters

    Case diameter

    Φ64mm

    Case material

    Stainless steel

    Scale range

    0 to 2bar abs.(customizable)

    Accuracy

    ±1.5%FS(+20℃ ±1℃)

    ±2.5%FS(-20℃~ +60℃) (gas phase)

    Ambient conditions

    -20° C to 60° C, relative humidity ≤ 95%RH

    Degree of protection

    IP65

    Leakage rate

    ≤ 1 × 10-9  Pa·m3/s  (Helium leakage inspection)

    Contact type

    Magnetic snap-action contacts (up to 3 sets, NO or NC)

    Process connection

    M20×1.5 (customizable)

    Maintenance connection

    M16×1.5 (customized and additional adapter needed to the calibrator or gas tank)

    Installation method

    Radial or Axial

    Insulation properties

    Insulation resistance: >100 MΩ  (500 V DC)

    Withstand voltage: 2kV, 50/60 Hz 1 min

    Contact electrical parameters

    Rated Power: 30VA

    Max. operating voltage

    380V

    Max. current

    1A

    Weight

    ≈ 0.6kg

    Pressure element

    Bourdon tubes

    Different measuring ranges
    Wide temperature range:-40° C to +60° C
    Measuring Medium:SF6 , Air, N2, SF6+N2 and other gases
    Remote transmission function
    Optional measurement accuracy:±1.0%FS(+20± 1℃) , ±2.5%FS(-20℃~ +60℃)(gas phase)