ZMJ60R Density Monitors is used to monitor the density of gas in closed containers, and can be widely used in medium voltage switchgear and ring network cabinet. It can display gas density on site, and reliably output SF6 gas density signal for remote monitoring and monitor- ing. It can be used in the new substation building and renovation and upgrading of existing substation.

    shop_iconsAdd ShopCart
    Contact us Download

    1

    SF6 Gas Insulated Ring Main Unit
    SF6 Gas Insulated Switch Gear

    Self-sealing: when this valve is disconnected from ei- ther side,it can seal and stop the flow of gas.
    Can withstand repeated usage.
    Can be used on outdoor switchgear.
    Can connect SF6 gas filling and vacuum pumping de- vices.
    Can connect SF6 gas recovery truck.

    Technical Parameters for Remote Module

    Operating voltage

    10~30VDC

     

     

    EMC Class

    IEC61000-4-2:Level 4

    IEC61000-4-3:Level 3

    IEC61000-4-4:Level 4

    IEC61000-4-5:Level 3

    IEC61000-4-6:Level 3

    IEC61000-4-8:Level 5

    Power consumption

    <0.5W

    Communication mode

    RS485

    Communication protocol

    Modbus RTU

    Baud rate

    9600bps

    Technical Parameters

    Technical Parameters

    Case diameter

    64mm

    Scale range

    0 ~ 2bar abs.(customizable)

    Accuracy of indication

    ±1.5%FS(+20±1℃) ; ±2.5%FS(-20℃~ +60℃)(gas)

    Degree of protection

    IP65

    Ambient condition

    -20℃ ~ +60℃  realative humidity ≤ 95%

    Leakage rate

    ≤ 1 × 10-9  Pa·m3/s  (Helium leakage inspection)

    Process connection

    M20 x 1.5 (customizable)

    Installation mode

    Radial or axial

    Electrical connection

    Pluggable connector, wire diameter 1 ~ 2.5 mm2 (1.5mm2  recommended)

    Insulation property(contact part)

    Insulation resistance: >100MΩ (DC500V)

    withstand voltage: 2kV, 50/60Hz, 1min

    Contact type

    Magnetic snap-action contact

    (Up to 3 set of contacts.s , NO & NC)

    Impact rating

    30 g

    Contact electrical parameters

    Rated Power:30VA

    Max switching voltage:380V

    Max switching current:1A

    Weight

    ≈ 0.9kg

    Pressure element

    Bourdon tube

    Measuring range
    Wider temperature range: -40℃ ~ +60℃ Outlet mode and cable length
    Installation method
    High altitude environment application
    Measuring Medium:SF6, Air, N2, SF6+N2 and other gases
    Optional measurement accuracy:±1.0%FS(+20± 1℃) , ±2.5%FS(-20℃~ +60℃)(gas phase)

    Make an free consultant

    Your Name*

    Phone Number

    Country

    Remarks*

    reset