Leave Your Message
about-us-banner
Products
01
Products Categories

ZMJ100P Density Monitor

ZMJ100P Density Monitors are used to monitor SF6 gas density in sealed tanks. They are applied to indicate gas density and to provide signal outputs when the density reaches preset threshold values. They are designed to monitor High Voltage systems. They can provide multi- ple solutions to support new substations and the reno- vation and upgrading of existing substations.

    iconAdd ShopCart
    Contact us Download

    pro1

    SF6 Gas Insulated Switchgear (GIS)
    SF6 Insulated Circuit Breakers
    SF6 Insulated Pole-Mounted Switch
    SF6 Insulated Transformers
    SF6 Insulated Current Transformers or Voltage Transformers
    SF6 Insulated Busbar Systems

    With temperature compensation, ensuring higher measuring accuracy.
    Suitable for indoor or outdoor installation.
    AISI 304 hermetically sealed stainless steel case.
    Gas line connecting parts are made of AISI 316 stain- less steel.
    The on-screen display value and output signals are im- mune from the impact of external environment, such as altitude.
    Electric contact switch design can ensure the precise and stable SF6 gas density monitoring.
    Up to 4 sets of switch contacts can achieve over-pres- sure alarm, dual alarm or double locking and many other options, making the monitoring more secure and reliable.

    Case diameter

    100mm

    Scale range

    -0.1 ~ 0.9MPa (customizable)

    Accuracy

    ±1.0%FS(+20±1℃) ,

    ±1.8%FS(-20℃~ +60℃)(gas phase)

    Degree of protection

    IP65

    Ambient conditions

    -20° C ~ +60° C, relative humidity ≤ 95%RH

    Leakage rate

    ≤ 1×10-9 Pa·m3/s(Helium leakage inspection)

    Process connection

    M20 × 1.5, (customizable)

    Installation method

    Radial or Axial

    Electrical connection

    Plug-in connection M20 X 1.5 sealing head

    cable size: 1.5mm2 recommended, upper limit 2.5mm2

    Insulation properties

    Insulation resistance:  >100 MΩ (500 V DC)

    Withstand voltage:2kV,50/60 Hz, 1min

    Contact type

    Magnetic snap-action switch

    80%Ag, 20%Ni, 10µm Gold plated

    Impact rating

    50g (oil-filled), 30g (non-oil-filled)

    Contact electrical parameters

    30W/50VA, 1A (upper limit )

    220VDC/380V 50/60Hz (upper limit )

    Watch glass

    Laminated safety glass

    Weight

    ≈ 1.0kg

    Pressure element

    Bourdon tube

    Oil-filled
    Withstand voltage: 2.5kV 50/60 Hz, 1min
    Wide temperature range :Optional-40 ℃ ~ +60 ℃ or -60° C ~ +60° C
    Measuring medium:SF6、Air、N2、SF6 +N2 and other gases
    Optional measurement accuracy:±1.6%FS(+20± 1℃), ±2.4%FS(-20℃~ +60℃)(gas phase)