+86-400-820-1296
RDH40 SF6 Gas Density and Dewpoint Transmitter - China Suppliers and Factory for High Voltage Systems Monitoring
Remote part of the main electrical performance indicators and specifications
| Operating voltage | 10~30VDC | EMC Class |
IEC61000-4-2: Level 4 IEC61000-4-3: Level 3 IEC61000-4-4: Level 4 IEC61000-4-5: Level 4 IEC61000-4-6: Level 3 IEC61000-4-8: Level 5 IEC61000-4-9: Level 5 IEC61000-4-10: Level 5 |
| Power consumption | <0.5W | ||
| Communication mode | RS485 | ||
| Communication protocol | Modbus RTU | ||
| Baud rate | 9600bps |
Technical parameters
| Pressure measuring range | 0 ~ 1.4MPa(customizable) |
| Dew measuring range | -50℃ ~ +20℃ |
| Accuracy of transmitter |
Temperature:±1℃ Pressure:±0.5%FS Pressure at 20℃: ±1.0%FS Dew:±3℃ |
| Degree of protection | IP65 |
| Ambient condition | -40℃ ~ +80℃ , Relative humidity ≤ 95%RH |
| Leakage rate | ≤ 1 x 10-9 Pa · m3/s (Helium leakage inspection) |
| Process connection | G1 (customizable) |
| Electrical connection | M12 x 1 Circular connector |
| Weight | 0.4kg |
Frequently Asked Questions
Q: What is the operating voltage range for this remote device?
A: The device operates within a voltage range of 10~30VDC, making it compatible with most industrial power supply systems.
Q: What communication protocol does the device support?
A: The device uses Modbus RTU protocol over RS485 communication interface with a baud rate of 9600bps, ensuring reliable data transmission in industrial environments.
Q: What is the accuracy of the pressure and temperature measurements?
A: The transmitter provides temperature accuracy of ±1℃, pressure accuracy of ±0.5%FS, and dew point accuracy of ±3℃. Pressure measurement at 20℃ has an accuracy of ±1.0%FS.
Q: Can the device withstand harsh environmental conditions?
A: Yes, the device has an IP65 protection rating and can operate in ambient temperatures ranging from -40℃ to +80℃ with relative humidity up to 95%RH.
Q: Is the pressure measuring range customizable?
A: Yes, while the standard pressure measuring range is 0 ~ 1.4MPa, it can be customized according to specific application requirements. The process connection G1 is also customizable.
Q: What EMC standards does the device comply with?
A: The device complies with multiple IEC61000-4 standards including Level 4 for ESD, EFT, and surge immunity, Level 3 for radiated immunity and conducted immunity, and Level 5 for magnetic field immunity, ensuring robust electromagnetic compatibility in industrial settings.

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series