+86-400-820-1296
MDK40 Density Switch

SF6 Gas Insulated RMU
SF6 Gas Insulated Switchgear
Temperature compensation ensures higher set point accuracy.
Can provide up to three sets of microswitch contacts allowing instant and accurate switching.
High shock resistance.
Normally closed contacts will not set a false alarm due to vibration.
|
Measuring range |
0 ~ 3 bar abs. (customizable) |
|
Accuracy of set point |
±2.0% @–30 ° C ~ +50 ° C |
|
Degree of protection |
IP42 |
|
Ambient conditions |
-25° C ~ +60° C, relative humidity ≤ 95%RH |
|
Leakage rate |
≤ 1 x 10-9 Pa · m3/s(helium leakage inspection) |
|
Process connection |
G1/4 (customizable) |
|
Installation method |
Axial |
|
Electrical connection |
Plug-in connection cable size: 0.2mm2 to 2.5mm2 |
|
Insulation properties |
Insulation resistance: >100 MΩ (DC 500V) Withstand voltage: 2kV, 50/60 Hz,1min |
|
Contact type |
Mirco switch |
|
Impact rating |
30g |
|
Contact electrical parameters |
30W/50VA, 1A (upper limit) 220VDC/380V 50/60Hz (upper limit) |
|
Weight |
0.3kg |
|
Pressure element |
Bellow |
Different measuring ranges Wide temperature range
Measuring medium:SF6、Air、N2、SF6+N2 and other gases
SF6 Online Monitoring System For GIS High Voltage Switch Distribution Room
In modern power systems, high-voltage switch distribution rooms are crucial components. In order to ensure the safe and reliable operation of power equipment, SF6 monitoring systems play an important role in the maintenance of high-voltage switch equipment. This article will explore the application and importance of SF6 monitoring systems in GIS high-voltage switch distribution rooms.
The Significance of SF6 Monitoring Systems in High-voltage Switch Distribution Rooms
High-voltage switches are one of the important equipment in power plants and distribution stations. In order to reliably deliver power projects to the state grid, it is necessary to ensure that high-voltage switches and other facilities operate normally and reliably. On high-voltage switch GIS equipment, SF6 maintenance gas density and trace moisture content are key to whether high-voltage switches can operate reliably.
In order to ensure the normal operation of high-voltage switches, it is necessary to ensure that the SF6 density is not less than a certain standard value. Therefore, the SF6 gas density of high-voltage switches must be monitored in real time. In the measurement of SF6 gas density, traditional methods mostly use pointer instruments and rely on on-site staff to obtain data manually. The disadvantage is that the measurement accuracy is poor and the reading is very inconvenient. In addition, incorrect readings may be caused by the carelessness of staff, which is not conducive to the standardized management of observation data. If a leak occurs, and the relative density does not drop to the alarm point, it will be difficult for the relevant staff to detect the leak, which is not conducive to recording the specific time and process of the leak. In serious cases, it may cause a great safety production accident.
In response to the above-mentioned demand for SF6 online monitoring in the high-voltage switch distribution room, the SF6 monitoring system is a design solution for the natural environment SF6, oxygen content, temperature and humidity detection provided in the GIS system workplace to avoid SF6 gas leakage causing low oxygen content and harm to relevant staff.
Practical Application of SF6 Monitoring Systems
In the high-voltage switch distribution room, the SF6 monitoring system can provide real-time gas density and humidity monitoring, avoiding the measurement deviation caused by gas release and re-inflation in traditional methods. Through online monitoring, the system can detect gas leakage problems in time and automatically alarm to ensure that timely measures are taken to avoid accidents.
·Accurate Gas Monitoring and Alarm Function
The SF6 monitoring system can accurately measure the gas content and moisture content. Through real-time data monitoring, it can immediately issue an alarm when the gas concentration exceeds the standard or oxygen is insufficient. In addition, the system also has temperature and humidity monitoring functions, which can record environmental changes in real time to ensure the stability of the distribution room environment.
·Automatic Ventilation and Remote Alarm
When the SF6 gas concentration is detected to be too high or the oxygen content is too low, the SF6 monitoring system can automatically start the exhaust fan for ventilation to ensure that the gas concentration returns to a safe range. At the same time, the system supports remote alarm function, and the staff can view the status of the distribution room in real time on the remote terminal, further improving safety and work efficiency.
·Convenient Data Management and Historical Query
The SF6 monitoring system provides a detailed historical data recording function, allowing users to query past data at any time for analysis and management. This not only helps maintenance personnel track changes in gas concentration, but also provides reliable data support for the long-term operation and maintenance of equipment.

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series