Leave Your Message
about-us-banner
Products
01
Products Categories

HM100PR Density Monitors

HM100PR Density Monitors are used to monitor SF6  gas density in sealed tanks. They are applied to provide alarm signal outputs when the density reaches preset values. Furthermore, it can transmit the real-time SF6  gas density data remotely, to achieve online remote monitoring function.. They are specifically designed for over 500kV EHV grade application field, adapting multilevel protection and full range of shielding measures to ensure the reliable operation of the products.

    shop_iconsAdd ShopCart
    Contact us Download

    1

    SF6 Gas Insulated Switchgear (GIS)
    SF6 Insulated Circuit Breakers
    SF6 Insulated Pole-Mounted Switch
    SF6 Insulated Transformers
    SF6 Insulated Current Transformers or Voltage Transformers
    SF6 Insulated Busbar Systems

    They adopt highly reliable protection circuit design, mul- ti-level isolation and filtering technology, thus effectively inhibiting the intrusion of conductive interference.
    They adopt the full-body shield design, stainless steel shield- ing shell, shielding junction box and shielding window glass, thus ensuring the ability of anti-electromagnetic radiation interference.
    They are able to adopt the optic fiber communication back- stage, thus avoiding data transmission losses from electro- magnetic interference.
    The use of high-precision SF6 density algorithm ensures that the background monitoring data coincides with those field instructions.
    They are compatible with ordinary SF6 remote products . They do not need other modifications in strong interference occasions.
    The temperature compensation device ensures higher meas- urement accuracy.

    Technical Parameters for Remote Module

    Power supply

    24V DC

    Anti-electromagnetic interference

    IEC61000-4-2

    IEC61000-4-3

    IEC61000-4-4

    IEC61000-4-5

    IEC61000-4-6

    IEC61000-4-8

    IEC61000-4-9

    IEC61000-4-10

    IEC61000-4-12

    IEC61000-4-17

    IEC61000-4-29

    level 4/A

    level 4/A

    level 4/A

    level 4/A

    level 3/A

    level 5/A

    level 5/A

    level 5/A

    level 4/A

    level 3/A 0.1s/A

    (8KV/15kV) (30V/m)

    (4KV)

    (+/-2Kv)

    (10V)

    (100A/m)

    (1000A/m)

    (100A/m) (4KV)

    (10%UN)

    (40%UT/70%UT)

    Power consumption

    < 2W

    Communication mode

    RS485

    Protocol

    ModBus RTU

    Baud rate

    9600bps

    Technical Parameters

    Technical Parameters

    Case diameter

    100mm

    Scale range

    -0.1 ~ 0.9MPa (customizable)

    Accuracy

    ±1.0%FS(+20±1℃) ,

    ±1.8%FS(-20℃~ +60℃)(gas phase)

    Degree of protection

    IP65

    Ambient conditions

    -20° C ~ +60° C, relative humidity ≤ 95%RH

    Leakage rate

    ≤ 1×10-9 Pa·m3/s (Helium leakage inspection)

    Process Connection

    M20 × 1.5, (customizable)

    Installation method

    Radial or Axial

    Electrical connection

    Plug-in connection M20 × 1.5 sealing head

    cable size: 1.5mm2  recommended, upper limit 2.5mm2

    Contact insulation performance

    Insulation resistance: >100MΩ (DC 500V)

    Withstand voltage: 2kV, 50/60Hz, 1min

    Contact type

    Magnetic snap-action switch

    80%Ag, 20%Ni, 10µm Gold plated

    Impact rating

    50g (oil-filled), 30g (non-oil-filled)

    Contact electrical parameters

    30W/50VA, 1A (upper limit)

    220VDC/380V 50/60Hz (upper limit)

    Watch glass

    Laminated safety glass

    Weight

    ≈ 1.2kg

    Pressure element

    Bourdon tube

    Oil-filled.
    Measuring medium: SF6, Air, N2, SF6 + N2 and other gases.
    Wide temperature range :Optional-40℃~ +60℃ or -60° C ~ +60° C.
    Optional measurement accuracy:±1.6%FS(+20±1℃) ±2.4%FS(-20℃~ +60℃)(gas phase).