+86-400-820-1296
High-Quality ZMJ60XDR Density Monitor from China Suppliers - Reliable SF6 Gas Density Monitoring Factory
Technical Parameters for Remote Module
| Operating voltage | 10~30VDC | EMC tests |
IEC61000-4-2: Level 4 IEC61000-4-3: Level 3 IEC61000-4-4: Level 4 IEC61000-4-5: Level 4 IEC61000-4-6: Level 3 IEC61000-4-8: Level 5 IEC61000-4-9: Level 5 IEC61000-4-10: Level 5 |
| Power consumption | <0.5W | ||
| Communication mode | RS485 | ||
| Communication protocol | Modbus RTU | ||
| Baud rate | 9600bps |
Technical Parameters
| Technical Parameters | |
| Scale range | -0.1 ~ 0.9MPa |
| Accuracy of set pressure point | ±10 kPa @ –30 ~ +60 ° C(gas) |
| Accuracy of indication | ±10 kPa @ –30 ~ +60 ° C(gas) |
| Accuracy of transmitter |
Pressure:±0.5%FS Temperature:±1℃ Pressure at 20℃: ±1.0%FS |
| Degree of protection | IP65 |
| Ambient condition | -30℃ ~ +60℃ , relative humidity:≤ 95%RH |
| Leakage rate | ≤ 1×10-9 Pa-m3/s (Helium leak inspection) |
| Process connection | M20 x 1.5 (customizable) |
| Installation method | Radial or Axial |
| Electrical connection | Pluggable connector, wire diameter 0.2~2.5 mm2 |
| Insulation property(contact part) |
Insulation resistance: >100MΩ (DC500V) Withstand voltage: 2kV, 50/60Hz, 1min |
| Contact type | Microswitch |
| Impact rating | 50g |
| Contact electrical parameters |
10(1.5)A, 250V AC 0.1(0.05)A, 250V DC |
| Watch glass | Laminated safety glass |
| Weight | ≈ 1.2kg |
| Pressure element | Bellow |
Frequently Asked Questions
Q: What is the operating voltage range for the remote module?
A: The remote module operates within a voltage range of 10~30VDC, ensuring compatibility with various industrial power systems.
Q: What communication protocol does the device support?
A: The device supports Modbus RTU protocol via RS485 communication mode with a baud rate of 9600bps, making it easy to integrate into existing industrial automation systems.
Q: What is the accuracy of the pressure measurement?
A: The accuracy of set pressure point and indication is ±10 kPa at temperatures ranging from –30 to +60°C for gas. The transmitter pressure accuracy is ±0.5%FS, and temperature accuracy is ±1℃.
Q: What is the degree of protection for this device?
A: The device has an IP65 protection rating, providing excellent protection against dust ingress and water jets, making it suitable for harsh industrial environments.
Q: What are the available installation methods?
A: The device can be installed either radially or axially, with a process connection of M20 x 1.5 (customizable) to accommodate different installation requirements.
Q: What EMC standards does the device comply with?
A: The device complies with multiple IEC61000-4 EMC standards including Level 4 for ESD, electrical fast transient, and surge tests, Level 3 for radiated immunity and conducted immunity, and Level 5 for power frequency magnetic field and damped oscillatory magnetic field tests.

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series