+86-400-820-1296
DDM60R Digital Density Monitor

SF6 Gas Insulated Swithchgear (GIS)
SF6 Insulated Circuit Breaker
SF Insulated Pole-Mounted Switch
SF6 Insulated Transformer
SF6 Insulation Current Transformer or Voltag Transformer
SF6 Insulated Bus System
Local digital display and control.
The microswitch is used as the signal output device to realize the free switching between normally open and normally closed points.
Temperature Compensated.
The alarm value can be set on site and can be ap- plied to cabinets with different alarm values.
Small size, installation interface can be customized, convenient and reliable.
RS485 bus interface, easy to do the system expan- sion, and to achieve telemetry, remote control func- tions. Strong EMC capability.
Remote part of the main electrical performance indicators and specifications
|
Operating voltage |
10~30VDC |
EMC Class |
IEC61000-4-2: Level 4 IEC61000-4-3: Level 3 IEC61000-4-4: Level 4 IEC61000-4-5: Level 4 IEC61000-4-6: Level 3 IEC61000-4-8: Level 5 IEC61000-4-9: Level 5 IEC61000-4-10: Level 5 |
|
Power consumption |
<1W(max. 1.5W) |
||
|
Communication mode |
RS485 |
||
|
Communication protocol |
Modbus RTU |
||
|
Baud Rate |
9600bps |
Technical parameters
|
Technical parameters |
|
|
Scale range |
-0.1 ~ 0.9MPa |
|
Accuracy of transmitter |
Pressure:±0.5%FS Temperature:±1℃ Pressure at 20℃: ±1.0%FS |
|
Degree of protection |
IP65 |
|
Ambient conditions |
-40℃ ~ +70℃ , relative humidity:≤ 95%RH |
|
Leakage rate |
≤ 1 × 10-9 Pa·m3/s (Helium leakage inspection) |
|
Process connection |
M20×1.5 (customizable) |
|
Installation method |
Radial or Axial |
|
Electrical connection |
Preset cable |
|
Insulation property(contact part) |
Insulation resistance: >100MΩ (DC500V) Power frequency withstand voltage: 2kV, 50/60Hz, 1min |
|
Contact type |
Magnetic holding electronic relay |
|
Impact rating |
30 g |
|
Contact electrical parameters |
Maximum switching voltage:380VAC/240VDC Maximum switching current:5A |
|
Watch glass |
Laminated safety glass |
|
Weight |
0.3kg |
Measuring Medium: SF6, Air, N2, SF6+N2 and other gases

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series