Leave Your Message
about-us-banner

Products

01

China ZMJ60XDR Density Monitor Suppliers - SF6 Gas Density Monitoring Solution from Reliable Factory

Introducing the ZMJ60XDR Density Monitors, a cutting-edge solution for monitoring SF6 gas density in sealed tanks. As a leading product from a prominent China factory, these monitors are essential for indicating gas density and providing signal outputs when preset threshold values are reached. Designed specifically for high voltage systems, our density monitors facilitate remote transmission of real-time SF6 gas density data, enabling online remote monitoring for improved safety and efficiency. Trusted by numerous suppliers, the ZMJ60XDR offers versatile solutions for new substations as well as the renovation and upgrading of existing facilities, ensuring reliable performance in critical applications
    shop_iconsAdd ShopCart
    Contact us Download

    Technical Parameters for Remote Module

    Parameter Value Test Type EMC Standards & Levels
    Operating voltage 10~30VDC EMC tests
    • IEC61000-4-2: Level 4
    • IEC61000-4-3: Level 3
    • IEC61000-4-4: Level 4
    • IEC61000-4-5: Level 4
    • IEC61000-4-6: Level 3
    • IEC61000-4-8: Level 5
    • IEC61000-4-9: Level 5
    • IEC61000-4-10: Level 5
    Power consumption <0.5W
    Communication mode RS485
    Communication protocol Modbus RTU
    Baud rate 9600bps

    Technical Parameters

    Specification Details
    Scale range -0.1 ~ 0.9MPa
    Accuracy of set pressure point ±10 kPa @ –30 ~ +60 ° C(gas)
    Accuracy of indication ±10 kPa @ –30 ~ +60 ° C(gas)
    Accuracy of transmitter Pressure: ±0.5%FS
    Temperature: ±1℃
    Pressure at 20℃: ±1.0%FS
    Degree of protection IP65
    Ambient condition -30℃ ~ +60℃, relative humidity: ≤ 95%RH
    Leakage rate ≤ 1×10-9 Pa-m3/s (Helium leak inspection)
    Process connection M20 x 1.5 (customizable)
    Installation method Radial or Axial
    Electrical connection Pluggable connector, wire diameter 0.2~2.5 mm2
    Insulation property (contact part) Insulation resistance: >100MΩ (DC500V)
    Withstand voltage: 2kV, 50/60Hz, 1min
    Contact type Microswitch
    Impact rating 50g
    Contact electrical parameters 10(1.5)A, 250V AC
    0.1(0.05)A, 250V DC
    Watch glass Laminated safety glass
    Weight ≈ 1.2kg
    Pressure element Bellow

    Frequently Asked Questions (FAQ)

    1. What are the electrical power requirements for the remote module?

    The remote module operates on a voltage range of 10 to 30VDC and has an energy-efficient power consumption of less than 0.5W.

    2. What communication protocol does the device use for data transmission?

    The device utilizes RS485 communication mode running the Modbus RTU protocol with a standard baud rate of 9600bps.

    3. What is the environmental protection level and temperature range for this equipment?

    It has an IP65 degree of protection. The ambient operating conditions range from -30℃ to +60℃ with a relative humidity of 95%RH or less.

    4. What is the measurement accuracy of the transmitter?

    The transmitter features a pressure accuracy of ±0.5%FS, a temperature accuracy of ±1℃, and a pressure accuracy of ±1.0%FS at 20℃.

    5. What are the installation options and process connection sizes available?

    The device supports either radial or axial installation methods. The standard process connection is M20 x 1.5, which can also be customized according to requirements.

    6. What type of safety glass and pressure element are used in the construction?

    The device is built with laminated safety glass for the watch glass and uses a high-durability bellow as the primary pressure element.

    Make an free consultant

    Your Name*

    Phone Number

    Country

    Remarks*

    reset