+86-400-820-1296
China ZMJ60XDR Density Monitor for SF6 Gas - Reliable Suppliers and Factory Solutions for High Voltage Systems
Technical Parameters for Remote Module
| Parameter | Value | EMC Tests | Standard |
|---|---|---|---|
| Operating voltage | 10 ~ 30 VDC | EMC Tests |
IEC61000-4-2: Level 4 IEC61000-4-3: Level 3 IEC61000-4-4: Level 4 IEC61000-4-5: Level 4 IEC61000-4-6: Level 3 IEC61000-4-8: Level 5 IEC61000-4-9: Level 5 IEC61000-4-10: Level 5 |
| Power consumption | < 0.5 W | ||
| Communication mode | RS485 | ||
| Communication protocol | Modbus RTU | ||
| Baud rate | 9600 bps |
Technical Parameters
| Technical Parameters | |
|---|---|
| Scale range | -0.1 ~ 0.9 MPa |
| Accuracy of set pressure point | ±10 kPa @ –30 ~ +60 °C (gas) |
| Accuracy of indication | ±10 kPa @ –30 ~ +60 °C (gas) |
| Accuracy of transmitter |
Pressure: ±0.5% FS Temperature: ±1 ℃ Pressure at 20 ℃: ±1.0% FS |
| Degree of protection | IP65 |
| Ambient condition | -30 ℃ ~ +60 ℃, relative humidity: ≤ 95% RH |
| Leakage rate | ≤ 1×10⁻⁹ Pa·m³/s (Helium leak inspection) |
| Process connection | M20 × 1.5 (customizable) |
| Installation method | Radial or Axial |
| Electrical connection | Pluggable connector, wire diameter 0.2 ~ 2.5 mm² |
| Insulation property (contact part) |
Insulation resistance: >100 MΩ (DC 500V) Withstand voltage: 2 kV, 50/60 Hz, 1 min |
| Contact type | Microswitch |
| Impact rating | 50 g |
| Contact electrical parameters |
10(1.5) A, 250V AC 0.1(0.05) A, 250V DC |
| Watch glass | Laminated safety glass |
| Weight | ≈ 1.2 kg |
| Pressure element | Bellow |
Frequently Asked Questions (FAQ)
Q
What is the operating voltage range of the remote module?
A
The remote module operates within a voltage range of 10 to 30 VDC, making it compatible with a wide variety of industrial power supply systems.
Q
What communication protocol does the remote module support?
A
The remote module uses RS485 as the communication mode and supports the Modbus RTU protocol at a baud rate of 9600 bps, which is widely used in industrial automation environments.
Q
What is the pressure measurement range and accuracy of the transmitter?
A
The scale range is -0.1 to 0.9 MPa. The transmitter accuracy is ±0.5% FS for pressure and ±1 ℃ for temperature. At 20 ℃, the pressure accuracy is ±1.0% FS.
Q
What is the degree of protection and what ambient conditions does the device support?
A
The device carries an IP65 protection rating, meaning it is dust-tight and protected against water jets. It is designed to operate in ambient temperatures from -30 ℃ to +60 ℃ with relative humidity up to 95% RH.
Q
How is the device installed and what process connection is available?
A
The device supports both radial and axial installation methods. The standard process connection is M20 × 1.5, and customizable options are available to suit different application requirements.
Q
What EMC standards does the remote module comply with?
A
The remote module has been tested against multiple IEC 61000-4 series standards, including levels 3 to 5 for electrostatic discharge, radiated immunity, electrical fast transient, surge, conducted immunity, and magnetic field immunity, ensuring reliable performance in electromagnetically harsh environments.

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series