+86-400-820-1296
China RDH40 SF6 Gas Density and Dewpoint Transmitter - Reliable Suppliers and Factory Solutions for Medium and High Voltage Systems
Remote Part of the Main Electrical Performance Indicators and Specifications
Operating voltage |
10 ~ 30 VDC |
EMC Class |
IEC61000-4-2: Level 4 IEC61000-4-3: Level 3 IEC61000-4-4: Level 4 IEC61000-4-5: Level 4 IEC61000-4-6: Level 3 IEC61000-4-8: Level 5 IEC61000-4-9: Level 5 IEC61000-4-10: Level 5 |
Power consumption |
< 0.5W |
||
Communication mode |
RS485 |
||
Communication protocol |
Modbus RTU |
||
Baud rate |
9600 bps |
Technical Parameters
Pressure measuring range |
0 ~ 1.4 MPa Customizable |
Dew measuring range |
-50℃ ~ +20℃ |
Accuracy of transmitter |
Temperature: ±1℃ | Pressure: ±0.5%FS Pressure at 20℃: ±1.0%FS | Dew: ±3℃ |
Degree of protection |
IP65 |
Ambient condition |
-40℃ ~ +80℃ | Relative humidity ≤ 95%RH |
Leakage rate |
≤ 1 x 10-9 Pa · m3/s (Helium leakage inspection) |
Process connection |
G1 Customizable |
Electrical connection |
M12 x 1 Circular connector |
Weight |
0.4 kg |
❓