+86-400-820-1296
China HM100PR Density Monitors for SF6 Gas - Reliable Factory Supply by Leading Suppliers
Technical Parameters for Remote Module
Power supply |
24V DC |
Anti-electromagnetic interference |
IEC61000-4-2 IEC61000-4-3 IEC61000-4-4 IEC61000-4-5 IEC61000-4-6 IEC61000-4-8 IEC61000-4-9 IEC61000-4-10 IEC61000-4-12 IEC61000-4-17 IEC61000-4-29 |
level 4/A level 4/A level 4/A level 4/A level 3/A level 5/A level 5/A level 5/A level 4/A level 3/A 0.1s/A |
(8KV/15kV) (30V/m) (4KV) (+/-2Kv) (10V) (100A/m) (1000A/m) (100A/m) (4KV) (10%UN) (40%UT/70%UT) |
Power consumption |
< 2W |
||||
Communication mode |
RS485 |
||||
Protocol |
ModBus RTU |
||||
Baud rate |
9600bps |
Technical Parameters
Technical Parameters |
|
Case diameter |
100mm |
Scale range |
-0.1 ~ 0.9MPa (customizable) |
Accuracy |
±1.0%FS(+20±1℃) ±1.8%FS(-20℃~ +60℃)(gas phase) |
Degree of protection |
IP65 |
Ambient conditions |
-20° C ~ +60° C, relative humidity ≤ 95%RH |
Leakage rate |
≤ 1×10⁻⁹ Pa·m³/s (Helium leakage inspection) |
Process Connection |
M20 × 1.5, (customizable) |
Installation method |
Radial or Axial |
Electrical connection |
Plug-in connection M20 × 1.5 sealing head Cable size: 1.5mm² recommended, upper limit 2.5mm² |
Contact insulation performance |
Insulation resistance: >100MΩ (DC 500V) Withstand voltage: 2kV, 50/60Hz, 1min |
Contact type |
Magnetic snap-action switch 80%Ag, 20%Ni, 10µm Gold plated |
Impact rating |
50g (oil-filled), 30g (non-oil-filled) |
Contact electrical parameters |
30W/50VA, 1A (upper limit) 220VDC/380V 50/60Hz (upper limit) |
Watch glass |
Laminated safety glass |
Weight |
≈ 1.2kg |
Pressure element |
Bourdon tube |

SF6 Gas Density Monitor
SF6 gas density transmitter
SF6 gas valve
SF6 Gas Detection Analyzer Series
Leakage Current Monitoring Series
Transformer Accessories Series