DT10 Density Transmitters are essential for monitoring SF6 gas density in sealed tanks, ensuring optimal performance in substations. As a leading factory in China, we provide innovative solutions tailored for both new substations and the renovation and upgrading of existing facilities. Our products are designed with precision and reliability, making us a preferred choice among suppliers in the industry. Trust our DT10 Density Transmitters to enhance your substation operations today.
    shop_iconsAdd ShopCart
    Contact us Download

    Technical Parameters

    Measuring Range 0 ~ 1.0 MPa
    Accuracy of Transmitter

    Temperature: ±1℃

    Pressure: ±0.5%FS

    Pressure at 20℃: ±1.0%FS

    Degree of Protection IP65
    Ambient Condition -40℃ ~ +70℃, Relative Humidity ≤ 95%RH
    Leakage Rate ≤ 1 × 10-9 Pa·m³/s (Helium leakage inspection)
    Process Connection M20 x 1.5 (customizable)
    Electrical Connection M12 x 1 Circular connector
    Weight 0.1 kg

    Technical Parameters for Remote Module

    Power & Communication
    Operating Voltage 10 ~ 30VDC
    Power Consumption < 0.5W
    Communication Mode RS485
    Communication Protocol Modbus RTU
    Baud Rate 9600 bps
    EMC Immunity Standards

    IEC61000-4-2 Level 4 (15kV)

    IEC61000-4-3 Level 3 (10V/m)

    IEC61000-4-4 Level 4 (4kV)

    IEC61000-4-5 Level 3 (1kV / 2kV)

    IEC61000-4-8 Level 5 (100A/m)

    IEC61000-4-9 Level 5 (1000A/m)

    IEC61000-4-10 Level 4 Class (30A/m)

    Frequently Asked Questions

    Q: What is the measuring range and accuracy of this pressure transmitter?
    The instrument provides a pressure measuring range of 0 to 1.0 MPa. It delivers a pressure measurement accuracy of ±0.5%FS (and ±1.0%FS at 20℃) alongside a temperature accuracy of ±1℃.
    Q: What interfaces and protocols are supported by the remote module?
    The remote module utilizes an RS485 communication interface operating with the Modbus RTU protocol at a factory baud rate of 9600 bps.
    Q: Can the process connection be customized?
    Yes. The standard mechanical process interface is M20 x 1.5, but custom process connection options are available upon request to fit specific installation requirements.
    Q: What are the environmental limits and ingress protection level?
    The unit is rated at IP65 protection grade, making it suitable for demanding conditions. It operates reliably within an ambient temperature range from -40℃ to +70℃ and relative humidity levels up to 95% RH.
    Q: What is the power consumption and supply voltage of the module?
    The remote module is engineered for energy-efficient operation with an operating voltage of 10 to 30 VDC and a low total power consumption of less than 0.5W.
    Q: What leakage testing standards does the device undergo?
    The unit passes stringent helium leakage testing ensuring a tight seal with a maximum leakage rate not exceeding 1 × 10⁻⁹ Pa·m³/s.